HMI PLC All In One 64MB RAM Clock Supported Pluggable Terminals
Advantage:
◆ Military level 32 bit CPU adopted, which is faster and more adapted to industrial environment of high electromagnetic interference.
◆ Special encryption, prevent illegal reading thoroughly. 8-bit encryption, 12345678 as password can thoroughly prevent reading of ladder logic program.
◆ Clock supported, rechargeable battery adopted.
◆ Default with 1 HMI download port, 2 PLC programming ports (RS232/MiniB USB port or Type-C), and one USB port.
◆ Support Mitsubishi programming protocol/MODBUS protocol/RS protocol/BD board protocol, easily realize PLC interconnection and communication with external devices.
◆ Convenient wiring. All wiring terminals adopt 3.81 pitch pluggable terminals, which is convenient for customers to use.
◆ Flexible use. More specifications and batches can be customized according to customer requirements.
Parameter:
Display  | Dimension  | 151*96*36mm  | 
Cutout size  | 143*86mm  | |
Type  | 5" TFT  | |
Feature  | 60K-color resistive touch screen, supports portrait display  | |
Memory  | RAM  | 64MB  | 
ROM  | NOR Flash 8MB  | |
CPU  | 32bit CPU 408MHz  | |
I/O  | DI/DO  | Max 12DI/12DO  | 
DI/DO level  | Input: Passive NPN, public terminal isolated  | |
DO type and load  | Relay MR/MOS tube, MOS tube: 2A/point, 4A/4 point COM, 5A/12 point COM; MR: 2A/point, 5A/12 point COM.  | |
Analog I/O (optional)  | Max 4AI/2AO  | |
AI type (optional)  | Thermocouple E/E_/K/K_/S/S_/T/T_/J/J_ / PT100/ PT1000/ NTC10K/ NTC50K/ NTC100K/ 0~10V/ 0~5V/ 0~20mA/ 4~20mA/ mixed  | |
AO type (optional)  | 0~10V /0~5V/ 0~20mA/ 4~20mA/ mixed  | |
High-speed function  | High-speed counting  | Single phase 6 channel 60KHz, or 2 AB 60KHz + 1 AB 10KHz, or 2 ABZ 60KHz + 1 AB phase 10 KHz  | 
High-speed pulse  | 8 channels, Y0-Y3 is 100KHz, Y4-Y7 is 10KHz. High-speed counting + high-speed pulse < 480KHz  | |
Connection  | HMI  | Type-C HMI download port  | 
/  | ||
PLC  | 1 TYPE-C, 1 RS232 (program port)  | |
1 RS485 or 2 RS485 COM ports (one of which is changed from the default RS232 port); 1 WIFI (occupy default RS232 port)  | ||
Software  | HMI  | Coolmay mView HMI Programming Software  | 
PLC  | Compatible with Mitsubishi GX Developer 8.86 and WORKS 2  | 
PID instruction format and parameter description:
Instruction format:

Parameter description:
Operand Type  | Content  | Data Type  | Word software component  | 
S1.  | Save data register number of the target value (SV)  | BIN16 bit  | D,R  | 
S2.  | Save data register number of the measured value (PV)  | BIN16 bit  | D,R  | 
S3.  | Save the data register number of the parameter  | BIN16 bit  | D,R  | 
D.  | Save data register number of the output register (MV)  | BIN16 bit  | D,R  | 
                                 
                             |